Crude Oil Brent (USD/Bbl) Fetching...

Welcome to ONGC Hazira Plant Intranet

Condensate fractionation unit

TABLE OF CONTENTS

CONTENTS                                                                                 PAGE

  1. Introduction

1.1  General                                                                             2

1.2  Design Basis

1.2.1        Design Capacity                                 3                     

1.2.2        Feed Specification                              4

1.2.3        Product Specification                          5

1.2.4        Utility Specification                              7

1.2.5        Effluent                                                11

1.2.6        Process flow diagram                         12

Effluent System Layout                       13-16

1.2.7        Material Balance                                 17-22

  1. Process design

2.1  Process description                                                          23-26

2.2  Utility System                                                                    27-28

2.3  Chemical system                                                              29-30

2.4  Effluent Summary                                                             31-32              

  1. Plant Shutdown procedure

3.1  General                                                                             33

3.2  Planned S/D-Short duration                                              33-34

3.3  Planned S/D-Long duration                                              34-36

3.4  Emergency S/D                                                                36-42

3.5  Compressor stopping procedure                                     43

3.6  Preparation of equipments for maintenance                    44-45

4.      Plant startup procedure

4.1  General                                                                             46       

4.2  Startup procedure                                                             46-47

4.3  CFU off gas startup sequence                                         48

4.4  CFU pumps startup procedure                                         49       

4.5  Consequences of not following specified methodology   50

  1. Modifications                                                                                                51
  2. Figure 5.1 (CFU Modification P & ID)                     Annexure II      52
  3. Trips & Alarm settings                                                                     53-55
  4. Operational tips                                                                                56-58
  5. Sketch of CFU Modification                                                                        59
  6. P&ID of Modification in CFU Tr. 72 & 76                                       60

Condensate fractionation unit

  1. Introduction

1.1             General:

Hazira Gas processing complex (HGPC) is a receiving point for South Bassein Gas from platforms BPA & BPB & JVG platforms along the sub sea route. The complex has a receiving terminal-stabilizes gas & stores associated condensate in the Slug-Catchers and processing facilities which includes Gas Sweetening & Dehydration, Condensate Fractionation, Dew Point Depression, Sulphur Recovery and associated offsites & utility systems.

Condensate which is received at the terminal along with sour gas needs to be sweetened by removal of dissolved hydrogen sulphide. The composition contains significant quantity of propane & butane which are to be recovered as LPG. Condensate Fractionation Unit (CFU) is designed to achieve these two objectives.

There are total seven numbers of CFU trains in HGPC-two in each of the phases-I, II, III & one in phase-IIIA. Each is of same designed capacity and similar operating methodology.


 

Condensate fractionation unit

1.2             Design Basis

1.2.1       Design Capacity:

The design capacity for the Gas Condensate Fractionation Units is 51.5 tons/hr or 75 m3/hr of sour condensate. This feed comes from Slug-catcher. There is also stream of sweet condensate from Dew point depression Units (DPD) which can be processed in CFU along with the slug-catcher condensate.

The plant has been designed such that the minimum running capacity for each Condensate Fractionation Unit is 40% of the Designed capacity i.e. 30 m3/hr. Each train is independently operated with all trains continuously in service.


 

Condensate fractionation unit

1.2.2        Feed Specifications: (Sour Condensate from the Slug-catcher)

Case

Case1

Case2

Case3

Case4

Pressure Kg/Cm2

Temp. o C

93.0

20.0

93.0

33.0

54.0

20.0

54.0

33.0

Component

Mole %

Kg mol/hr

Mole %

Kg mol/hr

Mole %

Kg mol/hr

Mole %

Kg mol/hr

N2

-

0.02

-

0.02

-

0.01

-

0.01

H2S

0.19

2.02

0.18

1.36

0.17

1.21

0.15

0.79

CO2

5.86

62.20

5.27

40.46

4.20

29.95

3.65

19.55

C1

37.85

401.92

34.68

266.56

22.91

163.28

20.93

112.03

C2

9.69

102.90

8.91

68.51

8.45

60.20

7.32

39.18

C3

12.42

131.89

11.75

90.32

14.07

100.31

12.26

65.08

iC4

3.83

40.73

3.77

28.99

5.11

36.40

4.56

24.42

nC4

5.94

63.07

5.95

45.74

8.27

28.98

7.56

40.44

iC5

2.39

25.42

2.54

19.49

3.66

26.05

3.61

19.31

nC5

2.70

28.72

2.91

22.40

4.18

29.82

4.24

22.67

C6

3.60

38.22

4.17

32.03

5.68

40.45

6.39

34.19

C7

4.10

43.54

5.02

38.59

6.34

45.22

7.69

41.12

C8

4.87

51.67

6.20

47.64

7.34

52.34

9.27

49.60

C9

2.52

26.82

3.29

25.29

3.74

26.67

4.81

25.77

C10

1.53

16.22

2.02

15.50

2.24

15.93

2.90

15.53

C11

1.73

18.42

2.31

17.73

2.52

17.97

3.29

17.60

C12

0.78

8.23

1.03

7.96

1.12

8.00

1.47

7.58

Total

100.00

1062.01

100.00

768.59

100.00

712.80

100.00

535.14

HC kg/hr

51690

41154

43641

35865

Water kg/hr

200

200

200

200

Mol. Wt.

48.67

53.54

61.23

67.02

Density kg/m3

545

551

595

597

Temp. o C

20

33

20

33

Pr. kg/cm2

93

93

54

54

*Stream composition depicted above is on a dry basis


 

Condensate fractionation unit

1.2.3        Product Specifications:

1.2.3.1       LPG:

Case

Case1

Case2

Case3

Case4

Pressure Kg/Cm2

Temp. o C

93.0

20.0

93.0

33.0

54.0

20.0

54.0

33.0

Component

Mole %

Kg mol/hr

Mole %

Kg mol/hr

Mole %

Kg mol/hr

Mole %

Kg mol/hr

N2

-

-

-

-

-

-

-

-

H2S

5

-

5.7

-

5.4

-

6.4

-

CO2

-

-

-

-

-

-

-

-

C1

-

-

-

-

-

-

-

-

C2

-

-

-

-

-

-

-

-

C3

48.63

80.43

48.09

58.25

45.55

70.06

44.78

47.25

iC4

19.43

32.14

19.48

23.60

20.23

31.12

20.14

21.25

nC4

31.86

52.70

32.33

39.16

34.14

52.51

34.55

36.46

iC5

0.07

0.12

0.09

0.11

0.08

0.12

0.48

0.51

nC5

0.01

0.01

0.01

0.01

-

-

0.05

0.06

C6

-

-

-

-

-

-

-

-

Total

100.00

165.40

100.00

121.13

100.00

153.81

100.00

105.53

HC kg/hr

8487

6224

7959

5479

Mol. Wt.

51.31

51.38

51.74

51.98

Density kg/m3

528

528

528

529

Temp. o C

43

43

45

45

Press. kg/cm2

15.5

15.5

15.5

15.5

1. Vapour pressure at 65 oC (Max.)                      16.8 Kg/cm2

2. Total Volatile Suphur PPM (Max.)                     20*

3. 95% distillate temp. at 760mm Hg                    2 oC

4. Copper strip corrosion (Max.)                           ASTM No.1 (Slight tarnish)

5. Dryness                                                                        No free water

6. Hydrogen Sulphide                                            20 ppm

* LPG shall be sweetened in the Caustic Wash Unit to meet IS-4576 specifications.

Condensate fractionation unit

1.2.3        Product Specifications:

1.2.3.2       Natural Gasoline

Case

Case1

Case2

Case3

Case4

Pressure Kg/Cm2

Temp. Deg C

93.0

20.0

93.0

33.0

54.0

20.0

54.0

33.0

Component

Mole %

Kg mol/hr

Mole %

Kg mol/hr

Mole %

Kg mol/hr

Mole %

Kg mol/hr

N2

-

-

-

-

-

-

-

-

H2S

-

-

-

-

-

-

-

-

CO2

-

-

-

-

-

-

-

-

C3

-

-

-

-

-

-

-

-

iC4

-

-

-

-

-

-

-

-

nC4

0.05

0.12

0.05

0.11

0.05

0.13

0.05

0.12

iC5

9.24

23.23

8.10

18.04

9.52

24.67

7.79

19.98

nC5

10.67

26.83

9.50

21.17

11.07

28.69

9.47

21.86

C6

14.79

37.19

14.07

31.34

15.40

39.90

14.63

33.80

C7

17.12

43.05

17.17

38.25

17.36

45.00

17.73

40.95

C8

20.46

51.42

21.30

47.47

20.15

52.24

21.44

49.53

C9

10.64

26.76

11.33

25.25

10.28

26.65

11.15

25.67

C10

6.44

16.20

6.95

15.49

6.14

15.93

6.73

15.53

C11

7.32

18.41

7.96

17.73

6.94

17.98

7.62

17.60

C12+

3.27

8.23

3.57

7.96

3.09

8.00

3.40

7.85

Total

100.00

251.44

100.00

222.81

100.00

259.19

100.00

230.98

HC kg/hr

27027

24360

27628

25154

Mol. Wt.

107.49

109.33

106.59

108.90

Density kg/m3

654

665

653

667

Temp. o C

45

45

45

45

Press. kg/cm2

5

5

5

5

1. Vapour pressure at 45 oC (Max.)                      0.65 Kg/cm2 a

* Free water content: Nil

Condensate fractionation unit

1.2.4        Utility Specifications:

1.2.4.1  Steam:

Steam (HP)

Minimum

Normal

Maximum

Design

Pressure Kg/cm2

34

35

37

40

Temp oC

Sat

Sat

250

560

Steam (MP)

Minimum

Normal

Maximum

Design

Pressure Kg/cm2

17

18

20

24

Temp. o C

Sat

Sat

230

250

Steam (LP)

Minimum

Normal

Maximum

Design

Pressure Kg/cm2

5.5

6

6.5

10

Temp. o C

Sat

Sat

180

200

1.2.4.2  Instrument Air:

Minimum

Normal

Maximum

Design

Pres. Kg/cm2

6.5

7.0

7.5

10

Dew point at –15 o C

-15

Oil Content

-Nil-

1.2.4.3  Plant Air:

Minimum

Normal

Maximum

Design

Pres. Kg/cm2

6.5

7.0

7.5

10

Dew point Deg C

Sat

Oil Content

-Nil-


 

Condensate fractionation unit

1.2.4.4  Cooling Water:

Supply pressure at grade kg/cm2a                          5

Return pressure at grade Kg/cm2a                         2.5

Supply temperature Deg C for exchanger design   33

Max. return temp. at any exchanger outlet              44

Turbidity in ppm                                          

Alkalinity, ppm                                                          15-20

Total hardness, ppm                                                300

Silica as SiO2, ppm                                                 125

Chlorides as Cl, ppm                                              

TDS, ppm                                                                850

PH                                                                            6.2-6.6

Conductivity at 20 Deg C, uohm/cm          

1.2.4.5  Service Water:

Supply pressure at grade kg/cm2a                          7.0

Return pressure at grade kg/cm2a                          -

Supply temperature oC for exchanger design         Ambient

Max. return temp. at any exchanger outlet              -

Turbidity in ppm                                                       5

Alkalinity, ppm                                                          15-20

Sodium as CaCO3 ppm                                          127

Bicarbonate as CaCO3, ppm                                  174

Calcium                                                                    67

Magnesium                                                              47

Silica as SiO4, ppm                                                 30

Chlorides as Cl, ppm                                               33

Suphate as SO4, ppm                                             33

TDS, ppm                                                                66

PH                                                                            7-8

Fe, ppm                                                                    0.3

Organic matter normally                                          Nil

Conductivity at 20 oC, uohm/cm     

Mech. Design pressure, Kg/cm2                             11

Mech. Design Temp., o C                                        65


 

Condensate fractionation unit

1.2.4.6  Inert Gas:

Minimum

Normal

Maximum

Design

Pres.Kg/cm2

6.0

7.0

-

10

Temp.o C

40

50

75

O2 %

0.5

H2 %

0.1

Dew point o C

-40 at 8 kg/cm2

CO %

0.1

N2 + CO2

Balance

Oil Content

-Nil-

Note

If this gas is not suitable for blanketing, fuel gas may be used

      

1.2.4.7  Fuel Gas:

Normal

Start up

Pres. Kg/cm2

4.5

4.5

Temp. o C

20-45

20-45

Molecular weight

19.0

20.94

Design Pressure

11

Composition:

C1

89.06

80.14

C2

5.55

7.70

C3

1.33

4.48

C4

0.15

1.80

C5

NIL

0.73

C02

3.90

5.14

N2

0.01

0.01

O2

NIL

NIL

H2O

NIL

SATURATED

SULPHUR(H2S)

2PPM

4PPM

OLEFINS

NIL

NIL

ACETYLENE

NIL

NIL

HEATING VALUE Kcak/kg, Net

10350

10460

Condensate fractionation unit

1.2.4.8  Boiler feed Water:

Supply pressure at grade kg/cm2a                         2.0

Temp. oC                                                                 Ambient

Note: Quality required for steam generation is acceptable.

1.2.4.9  Methanol:

Normal

Mech. Design

Pres.Kg/cm2

3.0

7.0

Temp. Deg C

Ambient

65

1.2.4.10    Electrical Power:

Service

Voltage

Phase

Frequency. Hertz

a. Motors upto 160 KW

415 V

3

50

Motors above 161 KW

6.6 KV

3

50

b. Lighting Dist.

240V

1

50

Instruments

110 V DC for interlocks

110 V AC through inverter (No break)

415, 240V

6.6 KV

110V DC

110V AC

Voltage variation

+6%

+10%

+10%

+1%

Frequency variation

+3%

+3%

-

+3%

        


 

Condensate fractionation unit

1.2.5       Effluents

  •       Released liquid hydrocarbons will be sent to closed blow down system.

  •       Released gaseous hydrocarbons will be sent to the central flare system.

Back Pressure of the Flare at battery limits end will be;

            Maximum= 1.8 Kg/cm2

            Minimum= 0.6 Kg/cm2

  •       Liquid waste effluents will be sent to a central waste water treatment plant.

1.2.6       Process flow Diagram (PFD) (See Annexure I, Figure 1.2.6):

The operating parameters shown in the PFD are for ideal operating conditions. Pressure & temperature profiles are liable to vary from train to train depending upon the prevailing conditions of the reboilers, trays, heat exchangers, feed quality and location of the instrumentation sensors etc.

The PFD also includes the modification of the drain line from the compressor suction KOD to LPG Column in the Trains 72 & 76.


 

Condensate fractionation unit

1.2.7          Material Balance for CFU

1.2.7.1    ( Case1: 54 kg/cm2 at 33 deg C)

Stream No.

1

2

3L

3V

Stream Name

Condensate from Slug catcher

Condensate surge drum vapour

Feed to Stripper

Liquid

Vapour

Component name

M Wt.

Mole %

Kg mol/hr

Mole %

Kg mol/hr

Mole %

Kg mol/hr

Mole %

Kg mol/hr

N2

28.01

-

0.01

-

-

-

-

-

0.01

H2S

34.08

0.15

0.79

0.10

0.01

0.13

0.53

0.21

0.25

CO2

44.01

3.65

19.55

7.27

0.75

1.97

7.98

9.13

10.82

C1

16.04

20.93

112.03

77.23

7.97

6.45

26.20

65.73

77.86

C2

30.07

7.32

39.18

7.56

0.78

5.92

24.07

12.09

14.33

C3

44.09

12.26

65.08

4.84

0.50

13.42

54.55

8.47

10.03

iC4

58.12

4.56

24.42

0.97

0.10

5.54

22.53

1.51

1.79

nC4

58.12

7.56

40.44

7.16

0.12

9.39

38.14

1.84

2.18

iC5

72.15

3.61

19.31

0.29

0.03

4.63

18.83

0.38

0.45

nC5

72.15

4.24

22.67

0.29

0.03

5.47

22.23

0.35

0.41

C6

86.17

6.39

34.19

0.19

0.02

8.36

33.96

0.18

0.21

C7

100.20

7.69

41.12

0.10

0.01

10.10

41.03

0.07

0.08

C8

114.22

9.27

49.60

-

-

12.20

49.56

0.03

0.04

C9

128.25

4.81

25.77

-

-

6.34

25.76

0.01

0.01

C10

142.28

2.90

15.53

-

-

3.82

15.53

-

-

C11

156.30

3.29

17.60

-

-

4.33

17.60

-

-

C12

170.33

1.47

7.58

-

-

1.93

7.85

-

-

Total

100.00

535.14

100.00

10.32

100.00

406.35

100.00

535.14

HC kg/hr

35865

226

32707

2932

Water kg/hr

200

Mol. Wt.

67.02

21.90

80.49

24.75

Density kg/m3

597

52.10

640

20.93

Temp. o C

33

35

27

27

Press. kg/cm2

54

52

18

18

            


 

Condensate fractionation unit

(1.2.7.1 Contd.) Material Balance for CFU (Case1: 54 kg/cm2 at 33 deg C)

Stream No.

4L

4V

5

6

Stream Name

Feed to LPG Column

LPG Feed to Caustic Wash Unit

NGL Product to Storage

Liquid

Vapour

Component name

M Wt.

Mole %

Kg mol/hr

Mole %

Kg mol/hr

Mole %

Kg mol/hr

Mole %

Kg mol/hr

N2

28.01

-

-

-

-

-

-

-

-

H2S

34.08

0.5ppm

-

6.3 ppm

-

6.4 ppm

-

-

-

CO2

44.01

-

-

-

-

-

-

-

-

C1

16.04

-

-

-

-

-

-

-

-

C2

30.07

-

-

-

-

-

-

-

-

C3

44.09

7.25

18.08

33.53

29.17

44.78

47.25

-

-

iC4

58.12

4.25

10.61

12.24

10.64

20.14

21.25

-

-

nC4

58.12

7.94

19.08

19.28

16.78

34.55

36.46

0.05

0.12

iC5

72.15

4.0

12.22

7.21

6.27

0.48

0.51

7.79

17.98

nC5

72.15

6.02

15.03

7.92

6.89

0.05

0.06

9.47

21.86

C6

86.17

10.82

26.99

7.82

6.81

-

-

14.63

33.80

C7

100.20

14.39

35.89

5.82

5.06

-

-

17.73

40.95

C8

114.22

18.41

45.94

4.13

3.59

-

-

21.44

49.53

C9

128.25

9.88

24.67

1.25

1.09

-

-

11.15

25.67

C10

142.28

6.07

15.15

0.43

0.38

-

-

6.72

15.53

C11

156.30

6.95

17.34

0.29

0.26

-

-

7.62

17.60

C12

170.33

3.12

7.78

0.08

0.07

-

-

3.40

7.85

Total

100.00

249.50

100.0

87.01

100.00

105.53

100.00

230.98

HC kg/hr

25056

5577

5479

25154

Water kg/hr

-

Mol. Wt.

100.442

64.10

51.98

108.90

Density kg/m3

577

22.07

529

667

Temp. o C

144

144

45

45

Press. kg/cm2

10.4

10.4

15.5

5

             


 

Condensate fractionation unit

(1.2.7.1 Contd.) Material Balance for CFU (Case1: 54 kg/cm2 at 33 deg C)

Stream No.

7

Stream Name

Vapour from stripper (Offgas)

Component name

M Wt.

Mole %

Kg mol/hr

N2

28.01

-

0.01

H2S

34.08

0.41

0.78

CO2

44.01

9.98

18.80

C1

16.04

55.26

104.6

C2

30.07

20.39

38.40

C3

44.09

9.20

17.33

iC4

58.12

1.63

3.07

nC4

58.12

1.99

3.74

iC5

72.15

0.42

0.79

nC5

72.15

0.38

0.72

C6

86.17

0.20

0.37

C7

100.20

0.09

0.16

C8

114.22

0.04

0.07

C9

128.25

0.01

0.01

C10

142.28

-

-

C11

156.30

-

-

C12

170.33

-

-

Total

100.00

188.31

HC kg/hr

5006

Water kg/hr

Mol. Wt.

26.58

Density kg/m3

20.73

Temp. o C

31

Press. kg/cm2

18.0


 

Condensate fractionation unit

1.2.7.2    Material Balance for CFU ( Case2: 93 kg/cm2 at 33 deg C)

Stream No.

1

2

3L

3V

Stream Name

Condensate from Slug catcher

Condensate surge drum vapour

Feed to Stripper

Liquid

Vapour

Component name

M Wt.

Mole %

Kg mol/hr

Mole %

Kg mol/hr

Mole %

Kg mol/hr

Mole %

Kg mol/hr

N2

28.01

-

0.02

0.01

0.01

-

-

0.01

0.01

H2S

34.08

0.18

1.36

0.14

0.13

0.17

0.75

0.21

0.48

CO2

44.01

5.27

40.46

7.56

7.15

2.71

12.11

.31

21.20

C1

16.04

34.68

266.56

76.22

72.14

9.15

40.82

67.45

153.60

C2

30.07

8.91

68.51

7.2

7.50

7.62

34.02

11.85

26.99

C3

44.09

11.75

90.32

5.03

4.76

15.28

68.18

7.63

17.36

iC4

58.12

3.77

28.99

0.5

0.90

5.65

25.22

1.26

2.87

nC4

58.12

5.95

45.74

1.19

1.13

9.24

41.21

1.49

3.40

iC5

72.15

2.54

19.49

0.29

0.27

4.16

18.55

0.29

0.67

nC5

72.15

2.91

22.40

0.28

0.26

4.83

21.54

0.26

0.60

C6

86.17

4.17

32.03

0.19

0.18

7.07

31.54

0.14

0.31

C7

100.20

5.02

38.59

0.12

0.11

8.59

38.35

0.06

0.13

C8

114.22

6.20

47.64

0.07

0.07

10.65

47.51

0.03

0.06

C9

128.25

3.29

25.29

0.02

0.02

5.66

25.26

0.01

0.01

C10

142.28

2.02

15.50

0.01

0.01

3.47

15.49

-

-

C11

156.30

2.31

17.73

-

-

3.97

17.73

-

-

C12

170.33

1.03

7.96

-

-

1.78

7.96

-

-

Total

100.00

768.59

100.00

94.64

100.00

446.24

100.00

227.71

HC kg/hr

41154

2106

33553

5495

Water kg/hr

200

Mol. Wt.

53.54

22.25

75.19

24.13

Density kg/m3

551

88

627

26.2

Temp. o C

33

39

27

27

Press. kg/cm2

93

80

25

25


 

Condensate fractionation unit

(1.2.7.2 Contd.) Material Balance for CFU (Case2: 93 kg/cm2 at 33 deg C)

Stream No.

4L

4V

5

6

Stream Name

Feed to LPG Column

LPG Feed to Caustic Wash Unit

NGL Product to Storage

Liquid

Vapour

Component name

M Wt.

Mole %

Kg mol/hr

Mole %

Kg mol/hr

Mole %

Kg mol/hr

Mole %

Kg mol/hr

N2

28.01

-

-

-

-

-

-

-

-

H2S

34.08

0.4 ppm

-

4.3ppm

-

5.7ppm

-

-

-

CO2

44.01

-

-

-

-

-

-

-

-

C1

16.04

-

-

-

-

-

-

-

-

C2

30.07

-

-

-

-

-

-

-

-

C3

44.09

6.33

12.89

31.76

45.56

48.09

58.25

-

-

iC4

58.12

3.58

7.18

11.45

16.42

19.48

23.60

-

-

nC4

58.12

6.64

13.12

18.09

25.95

32.33

39.16

0.05

0.11

iC5

72.15

4.10

8.22

6.92

9.93

0.09

0.11

8.10

18.04

nC5

72.15

5.06

10.14

7.69

11.04

0.01

0.01

9.50

21.17

C6

86.17

9.67

19.39

8.33

11.95

-

-

14.07

31.34

C7

100.20

14.08

28.22

6.99

10.03

-

-

17.17

38.25

C8

114.22

19.68

39.45

5.59

8.02

-

-

21.30

47.47

C9

128.25

11.26

22.58

1.86

2.67

-

-

11.33

25.25

C10

142.28

7.23

14.50

0.69

0.99

-

-

6.95

15.49

C11

156.30

8.49

17.02

0.50

0.71

-

-

7.96

17.73

C12

170.33

3.88

7.77

0.13

0.19

-

-

3.57

7.96

Total

100.00

200.48

100.00

143.46

100.0

121.13

100.00

222.81

HC kg/hr

21022

9562

6224

24360

Water kg/hr

-

Mol. Wt.

104.86

65.65

51.38

109.33

Density kg/m3

570

22.74

528

665

Temp. o C

156

156

43

45

Press. kg/cm2

10.4

10.4

15.5

5

           


 

Condensate fractionation unit

(1.2.7.2 Contd.) Material Balance for CFU (Case2: 93 kg/cm2 at 33 deg C)

Stream No.

7

Stream Name

Vapour from stripper (Offgas)

Component name

M Wt.

Mole %

Kg mol/hr

N2

28.01

-

0.01

H2S

34.08

0.37

1.23

CO2

44.01

10.10

33.31

C1

16.04

58.91

194.42

C2

30.07

18.49

61.01

C3

44.09

8.28

27.31

iC4

58.12

1.36

4.49

nC4

58.12

1.62

5.34

iC5

72.15

0.32

1.07

nC5

72.15

0.29

0.96

C6

86.17

0.16

0.51

C7

100.20

0.07

0.23

C8

114.22

0.03

0.10

C9

128.25

-

0.02

C10

142.28

-

-

C11

156.30

-

-

C12

170.33

-

-

Total

100.00

330.91

HC kg/hr

8464

Water kg/hr

Mol. Wt.

25.65

Density kg/m3

28.16

Temp. o C

31

Press. kg/cm2

25


 

Condensate fractionation unit

2.0             PROCESS DESIGN

2.1             PROCESS DESCRIPTION

Condensate Fractionation Unit is designed to remove H2S and to recover LPG & NGL from slug-catcher condensate.

The fractionation Unit consists of

-Condensate receiving system

-H2S Stripper

-Condensate-Offgas compression

-LPG Column.

                       

2.1.1       Condensate Receiving System

The condensate as it comes from the slug-catcher is heated in a condensate preheater (E701) and received in Surge Drum (V701) under level control through LCVs LV1101 & LV1106. The preheater uses LP steam to heat the condensate upto 33 oC to 36 oC to avoid any hydrate formation. Hydrate formation is possible if there is high pressure drop across control valves.

The flash vapour from the surge drum V701 is taken to gas sweetening unit directly (bypassing compressor) when condensate inlet pressure is at 80 kg/cm2 or more. Below 80 kg/cm2, the pressure is maintained 2 kg/cm2 below the inlet pressure in the surge drum to allow differential for incoming liquid and the vapour is routed through the compressor system.

Any free water droplets get separated in the surge drum and collect in boot of V701. Water level is drained through interface level control mechanism. The condensate in the surge drum V701 is taken into Condensate Transfer pumps P701A/B (one operating & one stand by). This pump is provided to generate sufficient head & flow to avoid any condensate flashing in the down stream Filter-Coalescer X701A/B.

Two unit of cartridge type Filter-Coalescer are provided (one operating & one stand by). The filtering elements of the filter are being used for filtering out any scale/dust/debris/Iron sulphides/black material which may entail during pre-commissioning/commissioning, pigging operation of the trunk lines.

Condensate fractionation unit

The coalescer element is used for removal of free water. The free water collected in the boot and is drained through interface level control mechanism. The condensate flows further through flow control valve FV1102 into the stripper column top tray. This is designed to maintain a back pressure to ensure that no flashing occurs in the filter chamber.

Dew Point Depression Unit’s condensate can also be processed in CFU besides LPG plant as and when required so.

2.1.2       H2S Stripper

Stripper Column C701 is designed to strip off H2S from the sour condensate such that the condensate at the bottom reaches maximum of 4 ppm H2S and to retain maximum C3 & C4 in the condensate at pressure of 18 to 18.5 kg/cm2 at the prevailing inlet pressure.

Feed to the stripper is a liquid at the upstream and flashes as liquid-vapour mixture in the space above the first tray of the column C701 of 61 valve type trays. The first 20 trays on the top section are single pass trays and the bottom section of 40 trays is double pass trays. The separated liquid trickles down the column and the vapour escapes from the top as offgas. The Offgas Stripper bottom liquid is pumped through P703A/B pumps to reboiler E702 via basket type filters X702A/B to remove any suspended particles which may foul the reboiler. However, in view to conserve energy, these filter pumps were stopped on experimental basis to observe the satisfactory operation if possible without them running. Effectively, these pumps & filter assembly were bypassed since 1999.

A kettle type reboiler E702 is provided at the Stripper C701 bottom which utilizes MP steam for heating. Steam flow is controlled through FV201 to ensure stripping vapour at 135 to 145 oC & thereby maintain stripper bottom temperature at 93 to 97 oC.

Bottom of C701 is sweet Condensate and is withdrawn from reboiler under level control cascaded with flow control valve FV202 to LPG Column C702


 

Condensate fractionation unit

2.1.3       LPG Column

            The stripper bottom liquid is taken to LPG column (C702) at 24th or 19th from top. This column has 60 trays and is designed to separate LPG (propane and butanes) from heavier components. The column operates at 9.7kg/cm2a pressure. This pressure has been chosen to keep overhead condensing temperature at 43 oC, so that cooling water can be used in the overhead condenser (E703).

Reflux ratio from 1.5-2.0 is maintained in the column depending upon the operating case. Butane recovery of more than 99.55 % is achieved at design reflux. LPG is taken as overhead liquid product through the LPG reflux and transfer pumps (P702 A/B) under level control of reflux drum (V702).                                                             

The column bottom has a thermo-siphon type reboiler (E704) using high pressure steam. Column bottom temperature varies from 175 to 185 oC depending upon operating case. NGL is withdrawn as bottom product and sent to Kerosene Recovery Unit for further processing or cooled to 45 oC by cooling water in NGL cooler E-705 and sent to storage in offsites as the case may be.

Most of Hydrogen sulfide (about 4 ppm) present in LPG column feed appears in LPG product resulting in 5 - 20 ppm concentrations. This LPG is sweetened in a caustic wash unit (Bubbling of LPG liquid in static bed of 15% caustic Soda solution) is off sites and sent to storage.

2.1.4       Off-gas Compression

            The stripper overhead vapor is taken to compressor suction K.O.Drum (V703). The surge drum flashed vapor is also combined with this stream. Two numbers reciprocating compressors 701 A/B (one operating & one standby) are provided in phase-I, II, III to compress this sour gas and form the feed to gas sweetening units. The compressor discharge gas is cooled to 45 oC using cooling water in exchanger E706. Gas temperature is selected about 10 oC higher than dew point to avoid condensation and production of sour condensate. This eliminates sour condensate recycle within the system. The cooled gas is sent to GSU through compressor discharge KOD drum V704.

Condensate fractionation unit

CFU off-gas compressor has been deleted for the Train 77 with the idea to utilize the existing under utilized compressor provided for this purpose under Phase I, Phase-II and Phase-III. CFU-off gas from this train shall be routed to the common suction header of these compressors (the compressors have been integrated.). The deletion of CFU off gas compressors has necessitated a slight change in the control scheme of the stripper column and the compression circuit. In the earlier trains the compressors have been provided with a pressure control at the suction and the stripper column floats on the suction pressure of the compressor. In the present train the stripper column shall operate at a slightly higher pressure and its pressure control shall be independent of the suction pressure control of the existing compressor.


 

Condensate fractionation unit

2.2             Utilities System

Condensate fractionation is located in a single block. For all process and utility lines, block boundary has been treated as B/L. All process and utility headers within B/L are common.

2.2.1       Steam/Condensate System

The steam condensate from all heaters/reboilers is taken through level control of steam Condensate pots. The high pressure condensate coming from the LPG column reboiler is flashed to produce MP steam in HP condensate flash drum (V708).

The MP condensate coming from (V708) and stripper reboiler (E702) is flashed to produce LP steam in MP condensate flash drum (V709). The final low pressure condensate from V709 and feed condensate heater (E701) will be sent back to B/L. ­

2.2.2       Flare System

A common flare header, flare K.O drum and flare blow down pumps are provided within B/L. All the hydrocarbon vapors/liquid collected from vents and pressure relief valves will go to flare K.O drum through flare header. From the gas goes over to a flare stack through an off site flare header. The liquid collected from flare K.O drum will be pumped to NGL Tank located in off sites.    

Tag Nos. of Flare KODs and Pumps:

1) 70V 756     P 752 A/B    Phase-I

2) 70V 761     P 761 A/B    Phase-II

3) 70V 781     P 781 A/B    Phase III

4) 70V 791     P 791 A/B    Phase IIIA

2.2.3       Instrument air, plant air, service water, inert gas, are received at B/L and supplied within unit through headers.

2.2.4       UTILITY CONSUMPTIONS

The normal utility requirements are listed in utility summary shown at the following page.


 

Condensate fractionation unit

UTILITY SUMMARY (Case: 54 Kg/cm2 a, 33 o C)

ITEM No.

SERVICE

Elec.

Power

Steam (Kg/cm2)

Water

Fuel

N2

Air

KW

HP(33)

MP(18)

LP(8)

Cond.

Loss

CW

DMW

SOFT

RAW

GAS

Oil

LA

PA

Kg/Hr

M3/hr

Kg/hr

Nm3/hr

Nm3/hr

E701

Condenser heater

1808

-1808

E702

Stripper reboiler

9097

E703

LPG col. condenser

232

E704

LPG thermo siphon reboiler

6766

E705

NGL Cooler

262

E706

Compressor discharge cooler

262

V705

LP cond. Flash Drum

V706

MP Cond. Flash Drum

V707

HP Cond. Flash Drum

-669

V708

MP Cond. Flash Drum

V709

MP Cond. Flash Drum

-1559

-13635

P701A/B

Cond. Transfer pump

26.9

P702A/B

LPG Reflux pump

22.6

P703A/B

Stripper bottom pump

21.9

Flare header

50

Instruments

200

Hose connections

10*

170*

170*

Total

Total

71.4

6766

8428

249

-15443

756

50

200

NOTE: The values marked with (*) represent intermittent utility and not included in the total figure


 

Condensate fractionation unit

2.3             Chemical System

2.3.1       Methanol System

A common methanol pot with methanol injection pumps are provided with B/L. Methanol will be received in the pot from offsite. This methanol is used to prevent/melt out hydrates in process unit during upset condition but since commissioning such problem has never been encountered in any CFU train.

        Quality             : Commercial

                               Quantity          :  3 m3 as initial fill. More methanol may be required depending upon process conditions encountered during starting and normal operation.

TAG NOS. OF METHANOL POTS & PUMPS:

1) 70 T 751                 P 753 A/B               Phase I

2) 70 T 761                 P 762 A/B               Phase II

3) 70 V 782                 P 782 A/B               Phase III

4) 70 V 792                 P 792 A/B               Phase IIIA

2.3.2       Other Chemicals

Other chemical required during construction and commissioning have to be arranged by contractor as per following list, and not limited to, depending upon specific needs.

- Lubricating oils etc. as per equipment vendor recommendation.


 

Condensate fractionation unit

2.4             Effluent Summary

Effluent from this plant is categorized as follows:

a) Liquid effluents comprising of process oily water, vessels drains and washings and storm water effluents.

b) Gaseous effluents from vessels and safety valve discharges

2.4.1       Liquid Effluents

In normal operation, there will be continuous and/or intermittent drainage of water from some vessels, drains, e.g surge drum, filter coalescers, and compressor KO. Drums, which is likely to be associated with dissolved hydrocarbons and hydrogen sulphide. Another source is occasional leakages/drippings of lubricating oils around the various rotating equipment like pumps and compressors.

During floor washings, waste water is generated which is likely to be contaminated with oil. During rainy seasons there are chances of rain/storm water also getting contaminated with oil.

All the above form liquid effluent. This effluent can be treated in centralized effluent treatment plant located in offsite area and hence, no primary treatment is necessary within process unit block. These effluents are collected in common Oily Water Sewer (OWS) system from where these are sent to a central waste water treatment plant.

The summary of liquid effluents coming out of the condensate fractionation unit is given in Table - 2.


 

Condensate fractionation unit

TABLE-2

LIQUID EFFLUENT SUMMARY

FOR CONDENSATE FRACTIONATION UNIT

DESCRIPTION

PROCESS DRAINS

UNIT FLOOR WASHING

CONTAMINATED RAIN WATER FROM PAVED  AREA

FLOW RATE,M3/HR AVG/PEAK

.5/1.0

-/15

NOTE-1

FREQUENCY OF FLOW CONTINUOUS/INTERMITTENT

CONT/INT

-/INT

-/INT

DURATION OF INTERMITTENT,HR

1.0

2.0

NOTE-1

TEMPERATURE, C

AMB

AMB

AMB

PRESSURE,KG/CM2a

ATM

ATM

ATM

COLOUR/ODOUR

CLEAR/H2S

CLEAR/-

CLEAR/-

SP.GRAVITY

1.0

1.0

1.0

VISCOSITY, Cp

0.7-1.0

0.7-1.0

0.7-1.0

pH

6-9

6-9

6-9

BOD mg/lit

300

100

300

COD, mg/lit

-

-

-

SUSPENDED SOLIDS, mg/lit

150

NOT AVAIL

NOT AVAIL

TOTAL DISSOLVED SOLIDS, mg/lit

NIL

DO

DO

TOTAL OIL  & GREASE CONTENT,PPM (MAX)

300

300

300

a) SP.GR. OF OIL

0.6-0.9

0.6-0.9

0.6-0.9

b) viscosity of oil, Cp

0.2-0.8

0.2-15

0.2-15

SULPHIDE CONTENT, mg/lit

5

-

-

PHENOL, mg/lit

--

---

--

NOTE:

  •       This data will be available from detailed engineering.

  •       The oil contamination will be light naphtha (highly volatile in process drain water and machine oil (lube oil) in floor washing and contaminated rain water.

Condensate fractionation unit

2.4.2       Gaseous Effluents

In normal circumstances there will not be any gaseous effluents, excepting small quantities from occasional gas venting from some equipment. However, during upset conditions, safety valves discharges will occur. Also, in event of one of condensate fractionation train shutdown, condensate stabilization unit will be operated and hence, continuous gaseous effluent will be generated.

For this a common elevated flare with ground box flare system has been provided in offsite. All the gaseous effluent will be routed through unit flare KO. Drum and diverted to offsite flare header for burning.

The gaseous effluent for various plants operating conditions are listed on Table - 3.

TABLE-3

GASEOUS EFFLUENTS FOR CONDENSATE FRACTIONATION UNIT

FIRE

POWER/COOLING WATER FAILURE

BLOCK DISCHARGE

MECHANICAL FAILURE

T/HR

M.WT.

C

T/HR

M.WT

C

T/HR

M.WT

C

T/HR

M.WT

C

124

27

60

89

45

50

755

50

-10

130

50

-10

Condensate fractionation unit

3.0          PLANT SHUTDOWN PROCEDURE

3.1          GENERAL

A planned shutdown is a non-emergency shutdown such as annual turn-around.

As the Condensate Fractionation Unit is connected with other downstream units, the process supervisors of this unit should be advised before any scheduled shutdown.

During a shutdown all equipment isolation valves should be closed to minimize the release of hydrocarbons.

Two types of normal shutdown (short duration and long duration) and purging procedures are presented in this chapter. The major difference between the two types of normal shutdown is that for the long duration shutdown, it is recommended that all the equipments be completely drained and purged.

3.2             PLANNED SHUT-DOWN (SHORT DURATION)

On a normal shutdown the feed to the unit should be slowly reduced in a stepwise manner to minimize disturbances to the downstream process units and utility system.

For shutdowns of a very short nature, i.e. less than a shift consideration should be given to blocking in the unit and storing the condensate in slug catcher.

3.2.1        Slowly reduce the slug catcher condensate feed to 40% design in steps of 5%   of design flow.

3.2.2  When the unit has been reduced to 40% of design flow start reducing the temperature of columns (C701, C702). This is done by reducing M.P steam to stripper reboiler E702 and H.P steam flow to LPG column reboiler E-704. If the off-gas from the surge drum (V701) is flow to the gas sweetening unit through the compressor by-pass line (4"-P-1103-1), switch over to the compressor suction drum when pressure starts falling below 80 kg/cm2a, set PIC1102 to 2 kg/cm2 below the condensate arrival pressure.

3.2.3  Close the stripper C701 feed by closing the FV1102.

3.2.4       Close the block valve on P701 A or B discharge line.

3.2.5        Stop the P701.

3.2.6       Close the block valves at the battery limit of LPG and NGL product.

3.2.7       Keep the LPG column reflux/transfer pump P702 A/B on circulation until LPG column has cooled down and level in reflux drum V-702 is at 20%.

3.2.8       Close shutdown valve SDV-1101.


 

Condensate fractionation unit

3.2.9       Slowly reduce the steam supply to heat exchangers, Condensate heater E701, Stripper reboiler E702, and LPG reboiler E704.

3.2.10  When the level in associated vessels have stabilized at 50%, block in the following control valves, LV-1101/1106, LV1102, LV1202.

3.2.11  The loads of compressor have been reduced to control the compressor   suction pressure and the pressure control valve PV1201A has been opened widely. Now, ensure total recycle during short period.

3.2.12  Stop the LPG column reflux/transfer pump P702 A/B when level in V702   has reduced 20%.

NOTE: Careful watch on all pressures, temperatures, levels and rotating equipments during this period is required. Make necessary adjustments so that restart can progress safety without too much delay.

3.3             PLANNED SHUT-DOWN (LONG DURATION)

For plant long duration shutdown, plant would be stopped as per procedure outlined for short duration.

Further all the equipment in the Condensate Fractionation Unit should be drained of liquid hydrocarbons and the plant depressurized to flare before purging all the equipment.

3.3.1       Keep LPG column C702 pressure at 10 kg/cm2a by adjusting the steam   flow to reboiler.

3.3.2       Slowly reduce the pressure of condensate surge drum (V-701) to 27 kg/cm2a.

3.3.3       Stop the compressors K701 A/B as per manufacturer’s instructions.

3.3.4       Start P701 A/B and pump out the condensate from the surge drum V701 until just before it evacuates.

3.3.5       Slowly transfer the liquid from coalescer filter X701A/B through FV102 bypass into the stripper column.

Note: Watch carefully when emptying X-701 A/B to prevent gas break through into the strippers, as it could disturb the trays and stripper, as it could disturb the trays and demister pad.

3.3.6       Start P703 A/B to transfer he liquid level in the bottom of stripper (C701) and reboiler to LPG column (C702). Stop P703 A/B just before it starts to evacuate.


 

Condensate fractionation unit

3.3.7       Start P702 A/B to pump out LPG level in reflux drum (V702) to caustic wash unit in offsites. Stop P702 A/B just before the level low-low is reached.

3.3.8       Transfer the liquid level from LPG column C702 and reboiler E704 to storage with system pressure.

3.3.9       Shut off the steam supply to E704 when levels are minimum.

3.3.10  Depressurise the entire unit to the flare system.

3.3.11  Drain any liquid levels to oily water sewer after checking that the system is      completely depressurized.

3.3.12  Close the block valves of suction line and discharge line of compressor K 701A/B.

3.3.13  Open the inert gas valve and purge out compressor with inert gas.

3.3.14  Turn spectacle blinds on suction & discharge of the compressor K701 A/B.

3.3.15  Purge the compressor with inert gas leave it under positive pressure.

3.3.16  Close the all drains and flare system.

3.3.17  Open block valves on inert gas connection line to X- 701 A/B and connect the inert gas to vessels from the hose stations. Purge out hydrocarbons from the unit.

3.3.18  Pressurize entire unit, up to 7.0 kg/cm2/a, with inert gas.

3.3.19  Depressurize the entire unit to flare system through all vent connections. Depressurize the unit to 0.1 kg/cm2g Repeat above steps 18, 19 more than three times until hydrocarbon content is below 0.5 vol%. Check and ensure that hydrocarbon content is below 0.5 vol % through the unit with a portable analyzer. Leave a pressure of 0.4 or O.7 kg/cm2g on the unit at the time final depressurizing is done. If hydrocarbon content is above 0.5 vol% depressurize to 0.1 kg/cm2g and repeat steps until hydrocarbon content is less than 0.5 vol%. Check hydrocarbon content in dead ends of pipes and ensure that hydrocarbon in liquid is blown through. Any hydrocarbon condensate accumulated in the vessel should be drained to the oily water sewer.


 

Condensate fractionation unit

3.3.20  Close all connections to flare when all lines and equipment have been purged.

3.3.21  Turn the spectacle blinds at unit battery limits to their closed position. The condensate fractionation unit, except flare and blow down system are now completely isolated and are ready for maintenance and inspection. The equipment and lines which shall not be opened for maintenance to be left at slight overpressure using inert gas or nitrogen. Maintenance personnel shall not enter any equipment without proper oxygen apparatus unless the unit has been purged entirely with air to displace all inert gas.        

3.4             EMERGENCY SHUT-DOWN

3.4.1       Types of Emergency Shut-down

Emergencies will generally require an immediate complete stoppage of operation with at least part of the plant shutdown and depressurized. In most instances, hydrocarbon must be eliminated to the maximum extent possible in the shortest time as determined by the urgency of the emergency. In some cases, the type of shutdown is complicated by the emergency situation itself, requiring in many cases a split-second decision by the operator.

Conduct all emergency shutdowns in the most economical manner possible with primary considerations for the safety of personnel, with secondary concern to safeguarding the equipment and still less priority reserved for products quality.

Determine the cause of the emergency including the exact situation: and if possible, revert to a normal shutdown at the first opportunity.

A unit shutdown system is provided to allow shutting down all incoming gas, treated and acid gas.

Emergency shutdowns may be caused by:

-Automatic shutdown following a programmed sequence and resulting for example from a product/utility failure.

-Manual shutdown entailed by an emergency or induced to avoid an accident.

Condensate fractionation unit

It is difficult to predict all the possible causes of emergency shutdown and to define, for each case, the actions to be taken.

Recommendations hereafter, are only partial guidelines; the actual shutdown procedure will be defined in function of the actual situation and operators troubleshooting capability.

3.4.2       Action during emergency shut-down;

3.4.2.1Low levels in condensate surge drum V-701. The following automatic actions will take place on LSLL1111 being activated.

  •       Stops   P701A/B

  •       Close FV1102.

The following manual action should be taken by operator;

  •       Put FIC1201 stripper reboiler on manual control and close it.

  •       Close LV1202 to maintain level in stripper C701.

  •       Reduce reflux to LPG column (C702) to maintain level in reflux drum (V­702)

  •       Maintain unit continuous until the level is restored in surge drum V701

3.4.2.2High level in surge drums V701.

The following automatic action will take place on LSHH-1108/LSHH1109.;    

  •       Close LV1101

  •       Close LV1106

  •       Shut off SDV1101

  •       Close steam supply valve FV1101 to condensate heater.

The following manual action should be taken by operator;

  •       Start P701 spare pump


 

Condensate fractionation unit

When level returns to normal condition, following actions should be taken;

·        Latch open shutdown valves.

·        Put LIC1101/1106 on manual control and feeding in condensate to the surge drum (V701).

·        Open FV1101 and supply the steam to condensate heater E701 then, control the temperature of condensate.

3.4.2.3Low water level in surge drum (V701) boot;

ILSLL1114 will be activated and shut off SDV1102 emergency shutdown valve automatically.

The following manual action should be taken by operator;

·        Put LV1102 on manual control and close it.

·        Unlatch the SDV1102 when interface level is established

3.4.2.4Pressure high in feed inlet to the surge drum

                      V701;

PSHH1108/1109 will be activated and following actions will happen automatically.

·        Shut off emergency shutdown valve SDV1101

·        Close steam control valve FV1101

·        Close LV1101/1106

The following actions should be taken by operator;

·        Reduce feed to the stripper by closing FV1102.

·        Open the compressor bypass line.

·        Check PV1102. If it has fail closed, open by-pass valve slowly.


 

Condensate fractionation unit

3.4.2.5Low temperature of Stripper feed;

TALL1109 will be activated and following actions will take place automatically;

·        Close emergency shutdown SDV1101

·        Close LV1106 & LV1101

·        Close steam control valve FV1101 to E701.

Following actions should be taken by the operator;

·        Decrease the feed flow to the stripper C701 by closing FV1102

·        Check steam system and the condensate system.

After the problem has been overcome;

·        Activate the start up switch located on the panel to bypass TALL1109.

·        Reset SDV1101

·        Reset LV1101 & 1106 manually.

·        Reset FV1101 manually.

·        Supply LP steam to E701

·        Slowly start feeding the condensate to Surge Drum.

3.4.2.6High pressure steam to condensate heater

PSHH 1106 will be activated and following actions will take place automatically;

·        Close SDV1101-Emergency shutdown valve.

·        Close LV1101 & LV1106

·        Close steam flow control valve FV1101.

Following actions to be taken by the Operator;

·        Reduce the feed flow to stripper

·        Check steam system for any tube failure

·        Bleed off excess steam pressure.

·        Reset SDV 1101 manually

·        Reset LV1101 & LV1106 manually

·        Reset FV1101 on to manual control & close it.

·        Bring unit to normal conditions.

Condensate fractionation unit

3.4.2.7Low level in slug catcher;

Trip signal will ensue at Gas Terminal and following actions to be followed;

·        Close emergency shut down valve.

·        Close LV 1101 & 1106

·        Close FV1101

Following actions should be taken by the operator;

·        Put FV1102 on manual control & close FV1102.

·        Stop condensate transfer pump P701A/B.

·        Slowly reduce steam flow and close FV1201, FV301.

·        Close Level control valves to retain liquid levels in columns & drums.

3.4.2.8Low water level in filter coalescer boot;

LSLL1117 & LSLL1120 in X701A & X701B respectively will actuate and following actions will take place automatically;

·        Shut off SDV1103 or SDV1104

·        Close ILV1103 or ILV1104.

After interface level is established, reset SOV manually and put controller on auto at 30% level.

3.4.2.9High pressure in the stripper Column C701;

PSHH1207 will be actuated and FV201 will close automatically.

Following actions should be taken by the Operator;

·        Check if compressor K701A/B is running OK.

·        Check DP across stripper- If high decrease feed rate.

·        Check column bottom temperature

·        Check condensate arrival pressure.

Condensate fractionation unit

3.4.2.10                    Low level in the stripper column

LSLL 1206 will be actuated and P703A/B will trip on interlock. Following actions to be taken by the operator;

·        Put FV1202 on manual control

·        Increase feed to stripper temporarily

·        Close LPG column level control valve LV1301/1302

·        Regulate FV1201

3.4.2.11                    High pressure in LPG column C702

PSHH1303 will be actuated and FV1301 will close on interlock. Following actions to be taken by the operator;

·        Check column overhead pressure

·        If too high and PV1301B is fully open, close PV1301A.

·        Check DP across the column C702

·        Check column bottom temperature TI1302

·        Check overhead temperature TI1304

·        Check reflux pump P702A/B

·        Check reflux control valve FV1301

3.4.2.12                    Instrument Air failure

The unit will automatically trip and short-duration shutdown procedure should be followed.

3.4.2.13                    Steam supply failure

·        LP steam failure: Reduce the feed such as to keep temperature above set point of TALL1110.

·        MP steam failure: Reduce the feed. If goes below 40% of the design flow, short duration shutdown to be followed.

·        HP steam failure: Reduce the feed to stripper and reduce LPG column reflux. Try matching feed with available heat supply. If goes below 40% of the design flow, short duration shutdown to be followed.

Condensate fractionation unit

3.4.2.14                    Cooling water failure;

Reduce the condensate feed and increase the LPG column reflux. Try to stabilize the LPG column. . If the feed goes below 40% of the design flow, short duration shutdown to be followed


 

Condensate fractionation unit

3.5             COMPRESSOR STOPPING PROCEDURE:

3.5.1       Unload the compressor by operating the unloader switch on the Local panel to unload the suction unloader-valves thereby reaching a state of no compression in the compressor cylinders.

3.5.2       Then the motor of the compressor is be stopped by the push button on the local panel.

3.5.3       Let the Auxiliary Lube oil pump run on auto mode for sometime (5 minutes or so). Stop the pump after switching it on manual mode.

The above three steps will bring compressor to Stand-by. For complete shutdown of the compressor system for maintenance work, following steps should be followed;

3.5.4       Close the discharge line isolation valve.

3.5.5       Close the suction line isolation valve.

3.5.6       Relieve the pressure in the compressor system to flare by the vent line provided.

3.5.7       Charge the system with nitrogen for purging.

3.5.8       For longer shut downs, isolate the cooling water supply to the lube oil cooler & cylinder jackets. Unless required so, the ethylene glycol solution provided for jacket cooling should not be drained.

3.5.9       Open the drain points provided at the bottom pockets of the compressor after the purging is done & the sample of the same is acceptable.

3.5.10  For longer duration shutdowns;

·        All cylinders/volume bottles should be drained from the bottom drain point provided to prevent any corrosion due to water condensation. Oil coating may be provided around to prevent rusting.

·        Lube oil circulation may be, on regular intervals, done by running the auxiliary lube oil pump in order to ensure lube oil distribution vital internal engine components.

Condensate fractionation unit

3.6             PREPARATION OF EQUIPMENTS FOR MAINTENACE:

3.6.1       Process Equipments: Tanks, Vessels etc.

Before opening any equipment, it should be thoroughly purged with nitrogen.

Operation to be carried out;

·        Isolation with valves & blinds

·        Draining & depressurization.

·        Flushing of inner volume with steam, water or inert gas (as required). Storage equipments such as Tanks & vessels should be washed with water.

·        Special care to be taken for instrumentation and the tapping & for the same.

·        Before opening any manhole cover, ventilation of the equipment & breathable air supply to be ensured by testing the inner space with gas detectors for HC or H2S & visual inspection for presence of any hazardous matter such as pyrophoric iron.

·        BA set/ safety gear should donned by the person entering the vessel after the clearance for entry.

NOTE: An open vent on the vessel top is ensured for continuous ventilation & drain point for any liquid trapped.

3.6.2       Precautions before handing over the equipment;

Following items should be checked by a competent authority/maintenance in charge/supervisor before handing over for maintenance job;

Condensate fractionation unit

              

·        Ensure proper isolation of the equipment.

·        Release any trapped pressure inside the equipment and check for any communication if any with the pressurized ends.

·        Positive isolation to be done in case of critical job involving hot work.

·        Remove obstructions in and around the area.

·        All utility supply lines such as steam lines to be isolated.

·        Provide proper tags on the critical points to avoid accidental operation.

·        Maintain progress/schedule of the job to ensure clear communication during shift change-over.

·        Before carrying out the hot job, ensure

¨      The check on any presence of explosive gases i.e. H2S & HC with the suitable detectors.

¨      Fire fighting devices/personnel in the area.

¨      Cover pits or drains with wet gunny bags.

¨      Spray hot surfaces in the vicinity with water.

  •       Ensuring above, the appropriate safety permit may be issued/endorsed.

  •       Presence of personnel as per the safety permit requirement should be ensured.

  •       Hot work should be suspended immediately on detection of abnormality or instruction on the paging system or instruction from the superior/incharge.

Condensate fractionation unit

4.0             PLANT STARTUP PROCEDURE

4.1             GENERAL

During the course of operation of the plant, it will be necessary to startup all or portions of the plant after shutting down for various reasons. After elaborate maintenance schedules such as Turnaround, the plant will have to be revived from a depressurized, ambient temperature state. Some portions of the plant will have to be restarted after a shutdown due mechanical, instrumentation or operational malfunction.

4.2             STARTUP PROCEDURE

4.2.1       In this procedure it has been assumed that the plant has been taken under shutdown for a short duration to allow maintenance on an equipment item or because of an interruption in the condensate feed supply.

4.2.2       The unit at this stage is assumed to have been fully precommissioned in accordance with precommissioning instructions, purged with inert gas, and repressurized to normal operating condition.

4.2.3       It is assumed that all the utility systems have been fully commissioned and are available to the unit. That all instruments have been checked and are ready to function in the automatic mode.

4.2.4       All piping and equipment in the unit should be lined up, and internal block valves and isolation valves should be opened as necessary.

4.2.5       In this stage process gas may be made available from the sweetening unit. Repressurize the surge drum V-701 with process gas to condensate header pressure.

4.2.6       Commission the process gas feed loop and condensate feed loop then set PIC1102 at 2 kg/cm2 below the condensate arrival pressure.

4.2.7       Slowly establish a flow to surge drum V701 by operating SDV1101.

4.2.8       Trip switch has to be by-passes for start-up. Put LV1101/LV1106 on manual control and slowly manipulate to establish a flow of condensate to the surge drum.

Condensate fractionation unit

4.2.9       Supply LP steam to condensate heater E701 and set TIC1101 to 39 °C watching for water hammer.

4.2.10  If the pressure of compressor suction side reaches to 18 kg/cm2a, set PIC1201A/B at 18 kg/cm2a and then start the K-701 A as per manufacturer’s instructions.

4.2.11  Start P-701A when a level is established in V-701.

4.2.12  Establish a flow through X701A to the LPG column (C701) via FV1102.

4.2.13  Establish a level in the bottom of C701.

4.2.14  Start reboiler pump P703A and establish a flow through filter X702A ­to the reboiler E702.In case P703 and X702 are bypassed, level will be established in E 702 directly from C701.   

4.2.15  Commission steam to E702 and condensate to the condensate flash drum

4.2.16  Set P1C1301 to 9.7 kg/cm2a.

4.2.17  Check bottom product for H2S content:

4.2.18  If it is less than 4.0 ppm, establish a flow to the LPG column C702.

4.2.19  Commission cooling water to E703 and E705 Condensate systems.

4.2.20  Establish a level in C702 base Commission steam to the reboiler E704 and condensate to the downstream.

4.2.21  Raise the temperature and pressure to normal conditions and set T1C1301 to give 160°C on automatic control.

4.2.22  Start the reflux pump P 702A and establish reflux now to give a top temperature of 56 °C with a reflux ratio of 2.0 to 2.8.

4.2.23  Send samples for analysis and fine tune the unit to give on specification product

4.2.24  When the products are on specification, start to increase the feed step wise by adjusting FIC1102 until the unit flow corresponds with the amount of condensate entering the slug catcher.


 

Condensate fractionation unit

4.3             CFU OFFGAS COMPRESSOR STARTUP SEQUENCE:

4.3.1       Ensure cleanliness around the area of compressor and motor.

4.3.2       Ensure proper fitting of flywheel guard.

4.3.3       Ensure suction and discharge valves are open.

4.3.4       Ensure no liquid is present in suction KOD and suction pulsation dampener by draining completely.

4.3.5       Ensure proper L.O. level in crank case.

4.3.6       Ensure sufficient level in Jacket cooling water tank.

4.3.7       Start auxiliary lube oil pumps of crank case in “man” mode and ensure proper pressure in L.O. header.

4.3.8       Start jacket cooling water pump and check for sufficient water pressure at cylinder jackets.

4.3.9       Press “TRIP RESET/SHUTDOWN RESET” button to clear all alarms on local panel.

4.3.10  Ensure loading selector switch selection is at “0 %”.

4.3.11  Check “READY TO START” indication on the panel

4.3.12  Inform Control Room and start the compressor and load the compressor sequentially to 50%, 75% and 100%.

4.3.13  Observe any abnormality like abnormal sound, overheating of loader valves, higher than normal amperage, overheating of cylinder jackets and high discharge temperature.

4.3.14  Put the auxiliary L.O. pump in” auto” mode and check it to have stopped.

In case already one compressor is running and change over is to be done then follow as below.

4.3.15  Follow the above steps from 1 to 11 for the second compressor also.

4.3.16  Inform C/R and start the compressor and start loading this compressor while unloading the first compressor.

4.3.17  Observe for any abnormalities.

4.3.18  Stop the first compressor when loading is at “0%”.

4.3.19  Ensure auxiliary L.O. pump is running at least for 15 minutes.


 

Condensate fractionation unit

4.4             STARTUP PROCEDURE FOR CENTRIFUGAL PUMPS IN CFU:

4.4.1       Ensure cleanliness around pump and motor.

4.4.2       Rotate the shaft to check for any mechanical jam.

4.4.3       Ensure that the discharge valve and minimum flow valve are closed and suction valve is open.

4.4.4       Check for sufficient level in L.O. cup of bearing housing.

4.4.5       Open casing vent to flare for priming the pump and close the same after completion of priming.

4.4.6       Ensure sufficient level in seal pot and check for any HC liquid present in the seal pot.

4.4.7       Check the cooling water lineup to the seal pot.

4.4.8       If instead of seal pot, separate liquid pumping system is present then check for sufficient level in seal tank and proper lineup of seal liquid pump, seal liquid cooler and main pump seal.

4.4.9       Start seal liquid pump and ensure proper discharge pressure.

4.4.10  Inform C/R and start main pump.

4.4.11  Open minimum flow valve.

4.4.12  Open discharge valve slowly observing the discharge pressure and motor amperage.

4.4.13  Open for any abnormal sound, high vibration, over amperage and over heating of motor and pump.

                                               

                                                In case of change over of pumps:

4.4.14  Follow the above steps and put the stand by pump in service.

4.4.15  Close the discharge valve and then minimum flow valve of the pimp to be stopped.

4.4.16  Stop the pump and check for the running pump taking full load.


 

Condensate fractionation unit

4.5              CONSEQUENCES OF  NOT FOLLOWING SPECIFIED METHODOLOGY ;

The plant is designed to be operated with specific operating procedures for running equipments. Not following the same may lead to damage of men and machinery .Some examples are as follows;

4.5.1       If compressor suction damper is not drained off liquid before starting the compressor, it may result in damage to the compressor components and may also cause explosion.

4.5.2       If suction valve is not opened before starting the compressor it may lead to collapsing of the equipment valve assembly in suction side.

4.5.3       If discharge valve is not opened before starting the reciprocating compressors it may lead to over pressurization and damage to the compressor components, HC leakage or explosion.

4.5.4       If centrifugal pump is not primed properly before starting the pump it    will cause vapour lock/cavitations and hence failure of mechanical seal assembly, overheating, damage to the impeller, fire or explosion.

4.5.5       If the pump is run without lube oil, it will result in damaging of the bearings/mechanical seal assembly and may lead to fire or explosion due to overheating.

4.5.6       Insufficient level of liquid in seal pot or excessive pressure in seal pot is an indication of seal leak. If not checked, the HC liquid may leak into the atmosphere creating hazardous condition. (I.e. explosion /fire hazard).           

Condensate fractionation unit

5.0             MODIFICATIONS:

5.1             Modification in the draining procedure of Compressor suction KOD (V703) in Trains 72 & 76; (See Annexure II; Figure 5.2)

The flashed vapours from the surge drum V701 and the Offgas from the Stripper Column C701 are combined and compressed. This compressed gas is further sent back to GSU upstream for sweetening as it is sour in nature. Condensable hydrocarbon vapour in the offgas is knocked off in the suction KOD V703 of the Compressor. On actuation of Level high switch LSH1209 in V703, the liquid needs to be drained off into the flare KOD before level high-high switch LSHH1210 is actuated resulting in tripping of the compressor.

In trains 72 & 76 (as shown in the Figure No.5.2) this liquid instead of being drained into the flare line is directed into the LPG Column. The modified drain line from K.O.D joins the feed line to LPG column from stripper reboiler at the downstream of the control valve FV1202. The SDV1104 provided on the drain line has to be opened from the C/R by pressing a push button PB104 provided. After draining the liquid level reaches at a point, actuating LSL1211, which as a result unlatches/closes SDV1104 automatically.


 

Condensate fractionation unit

6.0             TRIP AND ALARM SETTINGS:

6.1             PRESSURE SWITCHES & ALARMS:

TAG No.

DESCRIPTION

SET POINT Kg/cm2

ACTION

PSH1105

Condensate feed pressure high

95/59

Alarm

PSH1107

Surge drum pressure high

81/55

Alarm

PSH1108

PSH1109

Surge drum pressure high-high

83/59

Close LV1101

Close LV1106

Close SDV1101

Close FV1101

PSL1110

Surge drum pressure low

74/44

Alarm

PSL1111

X701A/B out pressure low

82/54

Alarm

PSH1206

Stripper bottom pressure high

26/19

Alarm

PSHH1207

Stripper bottom pressure high-high

28/21

Close FV1201

PSH1208

V703 Comp. suction pressure high

25/18

Alarm

PSL1209

V703 Comp. suction pressure low

21/14

Alarm

PSHH1106

LP steam pr. To E701 high-high

7

Close LV1101

Close LV1106

Close SDV1101

Close FV1101

PSH1302

LPG Column bottom pressure high

11

Alarm

PSHH1303

LPG Column bottom pressure high-high

12

Close FV1301


 

Condensate fractionation unit

           

6.2             TEMPERATURE SWITCHES & ALARMS

TAG No.

DESCRIPTION

SET POINT (oC)

ACTION

TSL1107

V701 Inlet Cond. Temp. low

28

Alarm

TSL1108

Stripper feed temp. low

22

Alarm

TSLL1109

Stripper feed temp. low-low

18

Close LV1101

Close LV1106

Close SDV1101

Close FV1101

TSH1110

V701 Inlet cond. Temp. high

43

Alarm

TSH1111

Off gas to B/L temp. high

50

Alarm

TSH1216

K701A Disch. Temp. high

135

Alarm

TSHH1217

K701A Disch, temp. High-High

150

Trip K701A

TSH1218

K701B Disch. Temp. high

135

Alarm

TSHH1219

K701B Disch, temp. High-High

150

Trip K701B

TSL1312                

E704 Outlet temp. low

205

Alarm

TSLL1313

E704 Outlet temp. low

200

Alarm

TSHH1314

E705 Outlet NGL temp. high-high

55

Close LV1301

Close LV1302


 

Condensate fractionation unit

           

6.3             LEVEL SWITCHES & ALARMS

TAG No.

DESCRIPTION

SET POINT (mm)

ACTION

LSH1107

V701 Level high

1300

Alarm

LSHH1108

LSHH1109

V701 Level high-high

V701 Level high-high

1400

1400

Close LV1101

Close LV1106

Close SDV1101

Close FV1101

LSL1110

V701 level low

250

Alarm

LSLL1111

V701 level low-low

150

Trip P701A/B

ILSH1112

V701 boot level high

2000

Alarm

ILSL1113

V701 boot level low

300

Alarm

ILSLL1114

V701 boot level low-low

200

Close SDV1102

Close LV1102

ILSH1115

X701A boot level high

Alarm

ILSL1116

X701A boot level low

Alarm

ILSLL1117

X701A boot level low-low

Close SDV1103

Close LV1103

ILSH1118

X701B boot level high

Alarm

ILSL1119

X701B boot level low

Alarm

ILSLL1120

X701B boot level low-low

Close SDV1104

Close LV1104

LSH1204

C701 Level high

1900

Alarm

LSL1205

C701 level low

300

Alarm

LSLL1206

C701 Level low-low

200

Trip P703A/B (redundant)

LSH1207

E702 Level high

1250

Alarm

LSL1208

E702 level low

250

Alarm

LSH1209

V703 Level high

500

Alarm

LSHH1210

V703 level high-high

1250

Trip K701A/B

LSL1211

V703 level low

150

Alarm

LSH1306

C702 level high

2000

Alarm

LSL1307

C702 level low

200

Alarm

LSH1308

V702 Level high

900

Alarm

LSL1309

V702 Level low

300

Alarm

LSH1310

V708 level high

1000

Alarm

LSL1311

V708 level low

150

Alarm

LSH1312

V709 level high

1000

Alarm

LSL1313

V709 level low

150

Alarm

LSH1801

V792 level high

2200

Alarm

LSL1802

V792 level low

250

Alarm

LSH1803

V791 level high

500

Alarm

LSL1804

V791 level low

200

Alarm

Condensate fractionation unit

7.0             OPERATIONAL TIPS:

                        Process Objectives:

                       

  •       To strip Hydrogen sulphide content from the condensate received from the offshore gas/condensate supply through slug-catchers at Hazira Gas terminal.

  •       To fractionate the condensate into LPG & NGL.

                        Principal of Operation:

  •       To achieve proper separation of lighter and heavier hydrocarbon through vapour-liquid equilibrium in the fractionation columns by establishing desired temperature profiles consistently.

                       

                        Process Variables:

  •       Operating variables affecting the stripping of H2S and fractionation of condensate are tabulated below;

A)                                                                             Stripper Column C701:

VARIABLE

DESIGNED OPERATING VALUE/RANGE

COMMENTS

Feed Rate

30-75 m3/hr

Higher feed rates will cause:

  •       Column Flooding

  •       Improper stripping of H2S

Feed Temperature

35-38 oC

Higher feed temp. leads to;

  •       Higher amount of vapour/condensable vapour carry over to suction KOD of the Off gas Compressors

Lower feed temp. leads to:

  •       Inadequate stripping of H2S in the column C701

  •       Demand rises in reboiler duty.

  •       Possibilty of hydrate formation at the flashing zones.


 

Condensate fractionation Unit

Operating Pressure

18 to 19 Kg/cm2

Higher pressure leads to:

  •       Improper stripping of H2S

  •       Demanding higher reboiler duty

Lower pressure leads to:

  •       Liquid carry over (column flooding)

  •       Decrease in volumetric efficiency of Offgas Compressors.

Reboiler vapour outlet temperature

130-140 oC

Higher temp. leads to;

  •       Liquid carryover along the stripping vapour (column flooding)

Lower temp. leads to;

  •       Increase in H2S content in the Stripper bottom feed to LPG Column

  •       Lighter HC will reach LPG column resulting in flaring from the LPG reflux top.

H2S Content of bottom liquid

< 4 ppm

Higher content will lead to off spec LPG product.

B)    LPG Column:

VARIABLE

DESIGNED OPERATING VALUE/RANGE

COMMENTS

Operating pressure

9.7 Kg/cm2

Higher pressure leads to;

  •       Demanding higher operating temperature to meet LPG specifications

Lower pressure leads to;

  •       Increase in load on the condenser

Column top Temperature

58-60 oC

Higher temp. leads to;

  •       Higher weathering of LPG product

Lower temp. leads to:

  •       Lower weathering temp. of LPG product Demand rises in reboiler duty.

  •       Reduction in overall product output (loss of C4 content alongwith NGL)

Condensate fractionation Unit

Reflux rate

1.5 times of LPG product (withdrawl)

Higher reflux leads to:

  •       Demanding higher condenser duty

Lower reflux leads to:

  •       Off spec LPG product with high weathering.

  •       Increase in reflux drum pressure. Hence flaring & thus product loss.

Reboiler vapour outlet temperature

175-185 o C

Higher temp. leads to;

  •       Higher LPG weathering.

  •       Higher condenser duty

Lower temp. leads to;

  •       Lower weathering temp. of LPG product Demand rises in reboiler duty.

  •       Reduction in overall product output (loss of C4 content alongwith NGL

C)                                                                                    Quality of Products:

PRODUCT

DESIGNED OPERATING VALUE/RANGE

COMMENTS

LPG:

1. RVP

2. Weathering

16.5 kg/cm2 at 65 o C

-2 to +2 o C

  •       Higher value of RVP indicates lighter LPG

  •       Higher value of weathering means heavier LPG

NGL:

1 RVP

2. Weathering

6.5kg/cm2 at 45 o C

0.5% Mole (Max)

  •       Higher RVP values means more lighter in NGL (especially C4)

-END OF THE DOCUMENT-